Generator set data sheet
- Engine Specifications 1.500 r.p.m.
- Rated Engine Output: 8,2kW prp ; 9kW standby
- Manufacturer: YANMAR
- Model: 3TNV80FNGGEH
- Engine Type: 4-stroke diesel
- Injection Type: Indirect
- Aspiration Type: Natural
- Number of cylinders and arrangement: 3-L
- Bore and Stroke: 80 x 84 mm
- Displacement: 1,27 L
- Cooling System: Liquid (water + 50% glycol)
- Lube Oil Specifications: SAE 3 class 10W30 / API grade CD,CF
- Compression Ratio: 23,1
- Fuel Consumption ESP: 2,82 l/h
- Fuel Consumption 100% PRP: 2,68 l/h
- Fuel Consumption 75 % PRP: 2,34 l/h
- Total oil capacity: 3,4 L
- Total coolant capacity: 4,4 L
- Governor Type Mechanical
- Air Filter Type Dry
- Diesel engine
- 4-stroke cycle
- Water-cooled
- 12V electrical system
- Water separator filter (visible level)
- Dry air filter
- Radiator with pusher fan
- Mechanical governor
- Hot parts protection
- Moving parts protection
- Generator: MECC ALTE
- Model: ECP28.2VS4C
- Poles: 4
- Connection type (standard): Star-series
- Mounting type: S-5 7"1/2
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Exciter system: Self-excited, brushless
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Single bearing
- Coupling system: Flexible disc
- Coating type: Standard (Vacuum impregnation)
- - SOUNDPROOFED VERSION.
- Steel chassis
- Anti-vibration shock absorbers
- Chassis with integrated fuel tank
- Fuel level gauge
- External emergency stop switch
- Bodywork made from high quality steel plate
- High mechanical strength
- Low noise emissions level
- Soundproofing provided by high-density volcanic rock wool
- Epoxy polyester powder coating
- Full access for maintenance (water, oil and filters, no need to remove the canopy)
- Watertight chassis (acts as a double barrier against liquid retention)
- Fuel tank drain plug
- Chassis drain plug
- Steel residential silencer -35db(A) attenuation.
- IP Protection according to ISO 8528-13:2016
- Fuel transfer pump (Optional)
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
- Battery charger (standard on gensets with automatic control panels)
- Heating resistor (standard on sets with automatic control panels)
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- Battery Switch (Optional)
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 400 ºC
- Exhaust Gas Flow: 2,4 m3/min
- Maximum allowed back pressure: 1000 mm H2o
- Exhaust Flange Size (external diameter): 50 mm
- - NECESSARY AMOUNT OF AIR.
- Intake air flow: 51,44 m3/h
- Cooling Air Flow: 0,693 m3/s
- Alternator fan air flow: 0,11 m3/s
- - STARTING SYSTEM.
- Starting power: 1,1 kW
- Starting power: 1,5 CV
- Auxiliary Voltage: 12 Vdc
- - FUEL SYSTEM
- Fuel Oil Specifications: Diesel
- Fuel Tank: 22 L
- Other fuel tank capacities: 100 L
- - DIMENSIONS.
- Length: 1.480 mm
- Height: 1.100 mm
- Width: 750 mm
- Maximum shipping volume: 1,22 m3
- Weight with liquids in radiator and sump: 462 kg
- Fuel tank capacity: 22 L
- Autonomy: 9 Hours
- Sound pressure level: 60 ± 2,4 dB(A)@7m
Length (A)14858.27
Width (B)7529.53
Height (C)11043.31
Weight with fluids in radiator and crankcase
462,00
1018.71
Length (A)14858.27
Width (B)7529.53
Height (C)127.550.20
Weight with fluids in radiator and crankcase
577
1272.285