Generator set data sheet
- Engine Specifications 1.500 r.p.m.
- Rated Engine Output: 242kW prp
- Manufacturer: SCANIA
- Model: DC9-71A(02-02)
- Engine Type: 4-stroke diesel
- Injection Type: Direct
- Aspiration Type: Turbocharged and after-cooled
- Number of cylinders and arrangement: 5-L
- Bore and Stroke: 130 x 140 mm
- Displacement: 9,3 L
- Cooling System: Coolant
- Lube Oil Specifications: ACEA E3,E4,E5 or E7
- Compression Ratio: 16:1
- Fuel Consumption 100% PRP: 59,98 l/h
- Fuel Consumption 75 % PRP: 46,5 l/h
- Fuel Consumption 50 % PRP: 31,43 l/h
- Lube oil consumption with full load: 0,2
- Total oil capacity: 38 L
- Total coolant capacity: 38 L
- Governor Type Electrical
- Air Filter Type Dry
- Inner diameter exhaust pipe: 90 mm
- Diesel engine
- 4-stroke cycle
- Water-cooled
- 24V electrical system
- Water separator filter (visible level)
- Dry air filter
- Radiator with pusher fan
- Radiator water level sensor
- HTW sender
- LOP sender
- Electronic governor
- Hot parts protection
- Moving parts protection
- Generator: MECC ALTE
- Model: ECO38 2L/4 A
- Poles: 4
- Connection type (standard): Star-series
- Mounting type: S-1 14"
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Exciter system: Self-excited, brushless
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Single bearing
- Coupling system: Flexible disc
- Coating type: Standard (Vacuum impregnation)
- - OPEN SET VERSION.
- Steel chassis
- Emergency stop button
- Oil sump extraction kit
- Anti-vibration shock absorbers
- Chassis with integrated fuel tank
- Fuel level gauge
- Fuel tank drain plug
- Steel industrial silencer -15db(A) attenuation
- Fuel transfer pump (Optional)
- Steel residential silencer -35db(A) attenuation. (Optional)
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Battery Switch
- Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
- Battery charger (standard on gensets with automatic control panels)
- Heating resistor (standard on sets with automatic control panels)
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 507 ºC
- Exhaust Gas Flow: 0,35 kg/s
- Maximum allowed back pressure: 100 mbar
- Heat dissipated by exhaust pipe: 635,05 KCal/Kwh
- - NECESSARY AMOUNT OF AIR.
- Intake air flow: 1000 m3/h
- Cooling Air Flow: 7,5 m3/s
- Alternator fan air flow: 0,533 m3/s
- - STARTING SYSTEM.
- Starting power: 5,5 kW
- Starting power: 7,48 CV
- Auxiliary Voltage: 24 Vdc
- - FUEL SYSTEM
- Fuel Oil Specifications: Diesel
- Fuel Tank: 449 L
- - DIMENSIONS.
- Length: 3.000 mm
- Height: 1.759 mm
- Width: 1.160 mm
- Maximum shipping volume: 6,12 m3
- Weight with liquids in radiator and sump: 2.385 kg
- Fuel tank capacity: 449 L
- Autonomy: 10 Hours
Length (A)300118.11
Width (B)11645.67
Height (C)175.969.25
Weight with fluids in radiator and crankcase
2385
5258.925